Indoor Unit (RA Models)
SiEBE18-526
82
Function
7.3
Programme Dry Function
Programme dry function removes humidity while preventing the room temperature from
lowering.
Since the microcomputer controls both the temperature and air flow volume, the temperature
adjustment and fan adjustment buttons are inoperable in this mode.
In Case of
Inverter Units
The microcomputer automatically sets the temperature and fan settings. The difference
between the room temperature at startup and the temperature set by the microcomputer is
divided into two zones. Then, the unit operates in the dry mode with an appropriate capacity for
each zone to maintain the temperature and humidity at a comfortable level.
Room temperature at
startup
Temperature (ON point)
at which operation starts
Frequency switching
point
Temperature difference
for operation stop
24°C
Room temperature at
startup
0.5°C
1.5°C
18°C
18°C
1.0°C
17°C
—
0.5°C
LHz
LHz
LHz
*
55Hz
*
55Hz
LHz indicates low frequency. Item marked with varies depending on models.
ON point
OFF point
5 min
5 min
Stop
Stop
Stop
Stop
Stop
Stop
Indoor unit fan
Extra-low air flow
Extra-low air flow
Low air flow
Low air flow
(R1359)
Frequency
switching
point
Compressor
control
Summary of Contents for Super Multi Plus D-Series
Page 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Page 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Page 249: ...Instruction SiEBE18 526 238 System Configuration...