Troubleshooting for Outdoor Unit
SiEBE18-526
316
Troubleshooting
7.22 Low Pressure Drop Due to Refrigerant Shortage or
Electronic Expansion Valve Failure
Remote
Controller
Display
U0
Applicable
Models
AII outdoor unit models
Method of
Malfunction
Detection
Short of gas malfunction is detected by discharge pipe temperature thermistor.
Malfunction
Decision
Conditions
Microcomputer judge and detect if the system is short of refrigerant.
H
Malfunction is not decided while the unit operation is continued.
Supposed
Causes
Out of gas or refrigerant system clogging (incorrect piping)
Defect of thermistor R2T or R4T
Defect of pressure sensor
Defect of outdoor unit PCB (A1P)
Troubleshooting
(Q0387)
Ts - Te > 20 °C?
Resistance
is normal when
measured with the
suction pipe thermistor
(R2T) and coil thermistor
(R4T) disconnected from
the outdoor unit
PCB.(3.5k
Ω
to 360 k
Ω
)
Out of gas or refrigerant
system is clogged. Requires
check of refrigerant system.
Replace the thermistor.
Replace the outdoor unit PCB
(A1P).
YES
NO
NO
Out of gas, closing of stop
valve or refrigerant system is
clogged.
Replace main outdoor unit
PCB (A1P).
YES
YES
NO
Cooling
Low pressure
is 0.25 MPa
or less.
The
voltage
of X45A pins (2)
and (3) on main
outdoor unit PCB
(A1P) is 0.8 VDC or less.
(Low pressure
sensor output
voltage)
NO
NO
YES
YES
Replace low pressure sensor.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for Super Multi Plus D-Series
Page 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Page 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Page 249: ...Instruction SiEBE18 526 238 System Configuration...