Troubleshooting for SkyAir Indoor Unit
Troubleshooting
283
5.13 Transmission Error (between Main and Sub Remote
Controller)
Remote
Controller
Display
U8
Applicable
Models
FFQ-B, FHQ-BU
Method of
Malfunction
Detection
In case of controlling with 2- remote controller, check the system using microcomputer if signal
transmission between indoor unit and remote controller (main and sub) is normal.
Malfunction
Decision
Conditions
Normal transmission does not continue for specified period.
Supposed
Causes
Transmission error between Main remote controller and Sub remote controller
Connection among “Sub” remote controllers
Faulty remote controller PCB
Troubleshooting
Turn the SS-1switch of one
remote control to "Main".
Turn OFF the power supply, and
restart operation
Turn OFF the power once and
restart operation.
Replace remote control PCB if
any error is generated.
Turn the SS-1switch of one
remote control to "Main".
Turn OFF the power supply, and
restart operation.
Controlling
with 2-remote control
Both SS-1
switches on remote
controls are turned
to "Sub"
SS-1switch on
remote control PCB
is turned to
"Main"
NO
NO
NO
YES
YES
YES
(S2042)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for Super Multi Plus D-Series
Page 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Page 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Page 249: ...Instruction SiEBE18 526 238 System Configuration...