Troubleshooting for Outdoor Unit
SiEBE18-526
300
Troubleshooting
7.7
Abnormal Discharge Pipe Temperature
Remote
Controller
Display
F3
Applicable
Models
AII outdoor unit models
Method of
Malfunction
Detection
Abnormality is detected according to the temperature detected by the discharge pipe
temperature sensor.
Malfunction
Decision
Conditions
When the discharge pipe temperature rises to an abnormally high level
When the discharge pipe temperature rises suddenly
Supposed
Causes
Faulty discharge pipe temperature
Faulty connection of discharge pipe thermistor
Faulty outdoor unit PCB
Troubleshooting
∗
Refer to thermistor resistance / temperature characteristics table on P326.
(Q0427)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Discharge pipe
temperature is 115°C
or higher.
Are
the characteristics
of the discharge pipe
thermistor normal?
(3.5~400K
Ω
)
Replace outdoor unit PCB A1P.
Replace the discharge pipe
thermistor.
NO
NO
Out of gas, compression defect,
etc. Defect of the refrigerant
system.
YES
YES
Summary of Contents for Super Multi Plus D-Series
Page 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Page 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Page 249: ...Instruction SiEBE18 526 238 System Configuration...