![Daikin Super Multi Plus D-Series Service Manual Download Page 57](http://html1.mh-extra.com/html/daikin/super-multi-plus-d-series/super-multi-plus-d-series_service-manual_2460573057.webp)
Refrigerant Circuit
SiEBE18-526
46
Refrigerant Circuit
1.2
BPMKS 967 A2B, B2B, A3B, B3B
No. in
refrigerant
system
diagram
Symbol
Name
Major Function
A
EVU
Electronic expansion valve
(for operating room)
Among EVA, EVB and EVC, the electronic expansion valve of operating room is called
EVU.
B
EVT
Electronic expansion valve
(for stopping room)
Among EVA, EVB and EVC, the electronic expansion valve of stopping room is called
EVT.
C
EVH
Electronic expansion valve
(Bypass)
While in oil return operation, used to adjust the refrigerant circulating rate of indoor
unit.
1
DGA
~ DGC
Thermistor (Gas pipe)
While in cooling operation, used to carry out the indoor unit SH control and cooling gas
pipe isothermal control.
2
DLA
~ DLC
Thermistor (Liquid pipe)
While in heating operation, used to carry out the indoor unit SC control.
3
R1T
Thermistor (Room temp.)
Used to detect room air temperature and instructs the capacity supply to BP unit.
4
R2T
Thermistor (Heat exchanger)
Used to detect heat exchanger temperature and carry out various protection functions
and controls of capacity.
5
R1T
Thermistor (Room temp.)
Used to detect room air temperature and instructs the capacity supply to BP unit.
6
R2T
Thermistor
(Heat exchanger 1)
Used to detect heat exchanger temperature and carry out various protection functions
and controls of capacity.
7
R3T
Thermistor
(Heat exchanger 2)
Used to detect heat exchanger temperature and carry out various protection functions
and controls of capacity.
Filter
Filter
Filter
Filter
Filter
RA indoor unit
SA indoor unit
EV
A
EV
H
EV
B
EV
C
(Q0403)
1
2
3
4
5
6
7
To
outdoor
unit
Summary of Contents for Super Multi Plus D-Series
Page 1: ...SiEBE18 526 D Series Service Manual Applied Models zSuper Multi Plus Heat Pump...
Page 12: ...SiEBE18 526 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 63: ...Refrigerant Flow for Each Operation Mode SiEBE18 526 52 Refrigerant Circuit...
Page 249: ...Instruction SiEBE18 526 238 System Configuration...