Field Setting
SiEBE18-526
118
Test Operation
3.2
Detail of Setting Mode
3.2.1 Cool / Heat Mode Switching
There are the following 2 cool/heat switching modes.
c
Set cool/heat separately for each outdoor unit system by indoor unit remote controller.
d
Set cool/heat separately for each outdoor unit system by cool/heat switching remote
controller.
c
Set Cool/Heat Separately for Each Outdoor System by Indoor Unit Remote Controller
Set outdoor unit PC board DS1-1 to “indoor” (factory set).
Set cool/heat switching to “individual” for “Setting mode 1” (factory set).
MODE
H1P
H2P
H3P
H4P
H5P
H6P
H7P
IND
TEST
MALFNC.
SLAVE
MASTER
C/H SELECT
C/H SELECT
F1
A
B
C
F2
F1
F2
F1 • F2
BP unit
(Q0405)
F1 • F2
BP unit
C/H SELECT R.C.
TO BP
Dip SW.
DS1-1
O
I
DEMAND
L.N.O.P.