![background image](http://html2.mh-extra.com/html/daikin/fcq35b7v1/fcq35b7v1_service-manual_4700521245.webp)
ESIE05-04
Field Settings
Part 4 – Commissioning and Test Run
4–21
3
4
5
1
Possible system
settings
The table below contains the possible system settings, which are displayed on the remote controller if
the TEST button is pushed twice shortly.
Changing the mode
settings
To enter the monitoring level and to change the maintenance mode settings, proceed as follows:
Size
Software
Type
Settings
Display
Settings
Display
35
35
5
FCQ
FJ
45
45
FHQ
HJ
60
63
FAQ
AJ
71
71
FFQ
GJ
100
100
FBQ
JJ
125
125
FUQ
3J
200
200
FDQ, FDEQ
UJ
250
250
—
Step
Action
1
Hold down the INSPECTION/TEST button for at least 4 s to enter the field setting mode.
2
Hold down the INSPECTION/TEST button for at least 4 s to enter the maintenance
mode.
3
Press the TEMPERATURE CONTROL buttons as many times as needed to select the
mode No. you want.
4
Press the TIMER SELECTION button as many times as needed to select the unit No. you
want.
5
Carry out the settings for modes 44 and 45. See “Maintenance Mode Settings” further in
this section.
6
Press the CONFIRMATION button to confirm the settings of modes 44 and 45.
7
Press the INSPECTION/TEST button to return to the normal operating mode.
Summary of Contents for FCQ35B7V1
Page 1: ...Service Manual ESIE05 04 R 410A Sky Air Indoor...
Page 2: ......
Page 20: ...ESIE05 04 1 2 Part 1 System Outline 3 1 1 5...
Page 62: ...General Outline ESIE05 04 1 44 Part 1 System Outline 3 1 1 4 5...
Page 78: ...ESIE05 04 1 60 Part 1 System Outline...
Page 112: ...Wiring Diagrams ESIE05 04 1 94 Part 1 System Outline 3 1 1 4 5...
Page 140: ...ESIE05 04 2 2 Part 2 Functional Description 3 1 2 5...
Page 164: ...ESIE05 04 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 206: ...Error Codes ESIE05 04 3 44 Part 3 Troubleshooting 3 1 3 4 5...
Page 224: ...Additional Checks for Troubleshooting ESIE05 04 3 62 Part 3 Troubleshooting 3 1 3 4 5...
Page 226: ...ESIE05 04 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 252: ...ESIE05 04 5 2 Part 5 Disassembly and Maintenance 3 1 5...
Page 384: ...Disassembly and Maintenance ESIE05 04 5 134 Part 5 Disassembly and Maintenance 3 1 5 5...
Page 390: ...ESIE05 04 vi Index 3 1 4 5 W Wiring diagrams Indoor units k 1 61...