ESIE05-04
Disassembly and Maintenance
Part 5 – Disassembly and Maintenance
5–39
3
5
1
5
2
Removing the drain pump
1
Cut the clamp material.
2
Pull the drain hose out.
3
Remove the 3 screws
on the drain pump
mounting plate.
4
Remove the 2 mounting
screws on the drain
pump.
5
Displace the drain pump
sideward to remove it.
Q
When removing the drain
pump, cut the following clamp
materials.
z
Clamp material securing the
drain pump lead wire to the
drain pump mounting plate.
z
Clamp material bundling the
drain pump lead wire and float
switch lead wire.
3
Removing the float switch
Q
When removing the float
switch, cut the following clamp
materials.
z
Clamp material securing the
drain pump lead wire to the
drain pump mounting plate.
z
Clamp material bundling the
drain pump lead wire and
float switch lead wire.
1
Reverse the drain pump
mounting plate which
was removed according
to the procedure
described on the
preceding page.
2
Remove the 1 screw,
displace the float switch
sideward, then
dismount the float
switch.
Step
Procedure
Points
Clamp material
Drain pump
Summary of Contents for FCQ35B7V1
Page 1: ...Service Manual ESIE05 04 R 410A Sky Air Indoor...
Page 2: ......
Page 20: ...ESIE05 04 1 2 Part 1 System Outline 3 1 1 5...
Page 62: ...General Outline ESIE05 04 1 44 Part 1 System Outline 3 1 1 4 5...
Page 78: ...ESIE05 04 1 60 Part 1 System Outline...
Page 112: ...Wiring Diagrams ESIE05 04 1 94 Part 1 System Outline 3 1 1 4 5...
Page 140: ...ESIE05 04 2 2 Part 2 Functional Description 3 1 2 5...
Page 164: ...ESIE05 04 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 206: ...Error Codes ESIE05 04 3 44 Part 3 Troubleshooting 3 1 3 4 5...
Page 224: ...Additional Checks for Troubleshooting ESIE05 04 3 62 Part 3 Troubleshooting 3 1 3 4 5...
Page 226: ...ESIE05 04 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 252: ...ESIE05 04 5 2 Part 5 Disassembly and Maintenance 3 1 5...
Page 384: ...Disassembly and Maintenance ESIE05 04 5 134 Part 5 Disassembly and Maintenance 3 1 5 5...
Page 390: ...ESIE05 04 vi Index 3 1 4 5 W Wiring diagrams Indoor units k 1 61...