Error Codes
ESIE05-04
3–38
Part 3 – Troubleshooting
3
1
3
4
5
2.6
Malfunctioning Capacity Setting (
AJ
)
Error code
AJ
LED indications
The table below shows the LED indications.
Error generation
The error is generated when the following conditions are fulfilled:
Causes
The possible causes are:
Q
Malfunctioning capacity setting adaptor connection
Q
Malfunctioning indoor unit PCB.
Capacity setting
adaptor
The capacity is set in the PCB’s memory IC. A capacity setting adaptor that matches the capacity of
the unit is required in the following case:
In case the indoor PCB installed at the factory is for some reason changed at the installation site, the
capacity will not be contained in the replacement PCB. To set the correct capacity for the PCB you
have to connect a capacity setting adaptor with the correct capacity setting to the PCB. The capacity
setting for the PCB will become the capacity setting of the adaptor because the capacity setting
adaptor has priority.
Operation
HAP (green)
HBP (green)
Normal
c
c
Malfunctioning
c
c
Condition
Description
1
Q
The unit is in operation.
Q
The PCB’s memory IC does not contain the capacity code.
Q
The capacity setting adaptor is not connected.
2
Q
The unit is in operation.
Q
The capacity that is set, does not exist for that unit.
Summary of Contents for FCQ35B7V1
Page 1: ...Service Manual ESIE05 04 R 410A Sky Air Indoor...
Page 2: ......
Page 20: ...ESIE05 04 1 2 Part 1 System Outline 3 1 1 5...
Page 62: ...General Outline ESIE05 04 1 44 Part 1 System Outline 3 1 1 4 5...
Page 78: ...ESIE05 04 1 60 Part 1 System Outline...
Page 112: ...Wiring Diagrams ESIE05 04 1 94 Part 1 System Outline 3 1 1 4 5...
Page 140: ...ESIE05 04 2 2 Part 2 Functional Description 3 1 2 5...
Page 164: ...ESIE05 04 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 206: ...Error Codes ESIE05 04 3 44 Part 3 Troubleshooting 3 1 3 4 5...
Page 224: ...Additional Checks for Troubleshooting ESIE05 04 3 62 Part 3 Troubleshooting 3 1 3 4 5...
Page 226: ...ESIE05 04 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 252: ...ESIE05 04 5 2 Part 5 Disassembly and Maintenance 3 1 5...
Page 384: ...Disassembly and Maintenance ESIE05 04 5 134 Part 5 Disassembly and Maintenance 3 1 5 5...
Page 390: ...ESIE05 04 vi Index 3 1 4 5 W Wiring diagrams Indoor units k 1 61...