Troubleshooting
ESIE05-04
3–26
Part 3 – Troubleshooting
3
1
3
4
5
1.7
Overview of Error Codes
Q
In the case of the shaded error codes, “inspection” is not displayed. The system operates, but be
sure to inspect and repair it.
Notes:
1
There is a possibility of open phase power supply, check power supply also.
2
Operation when a malfunction occurs may differ according to the model.
Malfunction Code
Contents/Processing
Remarks
A1
Failure of PC board ass’y for indoor unit
A3
Malfunction of drain water level system
A6
Indoor unit fan motor overload / overcurrent / lock (Note 1)
AF
Abnormal drain water level
Activation of float switch during compressor off.
AJ
Failure of capacity setting
Either capacity data is set incorrectly, or capacity
has not been set for the data IC
C4
Malfunction of heat exchanger temperature
sensor system
C5
Malfunction of gas piping temperature sensor
system
C9
Malfunction of suction air temperature sensor
system
CC
Malfunction of humidity sensor system
FCQ-D only.
CJ
Malfunction of remote control air temperature
sensor system
Failure of remote controller air thermistor.
Unit can be operated by indoor unit thermistor.
U4/UF
Failure of transmission (between indoor and
outdoor unit)
Transmission between indoor and outdoor unit is
not being correctly carried out. (Note 1, Note 2)
U5
Failure of transmission (between indoor unit and
remote controller)
Transmission between indoor and remote
controller is not being correctly carried out.
U8
Failure of transmission (between “main” and
“sub” remote controller
Transmission between “main” and “sub” remote
controller is not being correctly carried out.
UA
Failure of fieldsetting
System fieldsetting error pair, twin, triple, double
twin or wrong capacity class.
UC
Address error of central remote controller
Summary of Contents for FCQ35B7V1
Page 1: ...Service Manual ESIE05 04 R 410A Sky Air Indoor...
Page 2: ......
Page 20: ...ESIE05 04 1 2 Part 1 System Outline 3 1 1 5...
Page 62: ...General Outline ESIE05 04 1 44 Part 1 System Outline 3 1 1 4 5...
Page 78: ...ESIE05 04 1 60 Part 1 System Outline...
Page 112: ...Wiring Diagrams ESIE05 04 1 94 Part 1 System Outline 3 1 1 4 5...
Page 140: ...ESIE05 04 2 2 Part 2 Functional Description 3 1 2 5...
Page 164: ...ESIE05 04 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 206: ...Error Codes ESIE05 04 3 44 Part 3 Troubleshooting 3 1 3 4 5...
Page 224: ...Additional Checks for Troubleshooting ESIE05 04 3 62 Part 3 Troubleshooting 3 1 3 4 5...
Page 226: ...ESIE05 04 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 252: ...ESIE05 04 5 2 Part 5 Disassembly and Maintenance 3 1 5...
Page 384: ...Disassembly and Maintenance ESIE05 04 5 134 Part 5 Disassembly and Maintenance 3 1 5 5...
Page 390: ...ESIE05 04 vi Index 3 1 4 5 W Wiring diagrams Indoor units k 1 61...