Specifications
ESIE05-04
1–48
Part 1 – System Outline
3
1
1
4
5
2.4
FFQ – B
Technical
specifications
The table below contains the technical specifications.
Electrical
specifications
The table below contains the electrical specifications.
Specification
FFQ25B7V1B
FFQ35B7V1B
FFQ50B7V1B
FFQ60B7V1B
Heat exchanger
Rows x stages x fin pitch
2x10x1.5 mm
Face area
0.269 m²
Tube type
HiXSS diam. 7
Fin type
Multi louver fin
Fan
Air flow rate cooling (high)
9.0 m³/min
10.0 m³/min
12.0 m³/min
15.0 m³/min
Air flow rate cooling (low)
6.5 m³/min
6.5 m³/min
8.0 m³/min
10.0 m³/min
Air flow rate heating (high)
9.0 m³/min
10.0 m³/min
–
15.0 m³/min
Air flow rate heating (low)
6.5 m³/min
6.5 m³/min
–
10.0 m³/min
Qty x model (rotor)
1 x QTS32C15M
Qty x model (motor)
1 x D16P52A23
Fan speed
2 steps
Fan type
Turbo fan
Refrigerant
Type
R410A
Safety and functional devices
Inline fuse (250V 5A)
Fan motor thermal protector
OFF: 130
+/- 5
°C
ON: 83
+/- 20
°C
Air filter
Removable/washable/mildew proof/long life (in decoration panel)
Temperature control
Microcomputer control
Weight
Unit
17.5 kg
Specification
FFQ25B7V1B
FFQ35B7V1B
FFQ50B7V1B
FFQ60B7V1B
Unit
Phase
1~
Voltage
230V
Frequency
50 Hz
Power consumption
73 W
84 W
97 W
120 W
Nominal running current
0.37 A
0.40 A
0.49 A
0.61 A
Fan motor
FLA (Full Load Amps)
0.60 A
0.70 A
No. of motors x output
1 x 55 W
Summary of Contents for FCQ35B7V1
Page 1: ...Service Manual ESIE05 04 R 410A Sky Air Indoor...
Page 2: ......
Page 20: ...ESIE05 04 1 2 Part 1 System Outline 3 1 1 5...
Page 62: ...General Outline ESIE05 04 1 44 Part 1 System Outline 3 1 1 4 5...
Page 78: ...ESIE05 04 1 60 Part 1 System Outline...
Page 112: ...Wiring Diagrams ESIE05 04 1 94 Part 1 System Outline 3 1 1 4 5...
Page 140: ...ESIE05 04 2 2 Part 2 Functional Description 3 1 2 5...
Page 164: ...ESIE05 04 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 206: ...Error Codes ESIE05 04 3 44 Part 3 Troubleshooting 3 1 3 4 5...
Page 224: ...Additional Checks for Troubleshooting ESIE05 04 3 62 Part 3 Troubleshooting 3 1 3 4 5...
Page 226: ...ESIE05 04 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 252: ...ESIE05 04 5 2 Part 5 Disassembly and Maintenance 3 1 5...
Page 384: ...Disassembly and Maintenance ESIE05 04 5 134 Part 5 Disassembly and Maintenance 3 1 5 5...
Page 390: ...ESIE05 04 vi Index 3 1 4 5 W Wiring diagrams Indoor units k 1 61...