Troubleshooting
ESIE05-04
3–22
Part 3 – Troubleshooting
3
1
3
4
5
1.6
Fault-diagnosis by Wireless Remote Controller
Introduction
Contrary to the wired remote controller, the wireless remote controller does not display the error code.
Instead, the operation LED on the light reception section flashes.
Checking
To find the error code, proceed as follows:
Step
Action
1
Press the INSPECTION/TEST button to select “inspection”. The equipment enters the
inspection mode. “0” flashes in the UNIT No. display.
0
INSPECTION/TEST