![Daikin FCQ35B7V1 Service Manual Download Page 71](http://html2.mh-extra.com/html/daikin/fcq35b7v1/fcq35b7v1_service-manual_4700521071.webp)
ESIE05-04
Specifications
Part 1 – System Outline
1–53
3
1
4
5
2.9
FAQ – B
Technical
specifications
The table below contains the technical specifications.
Electrical
specifications
The table below contains the electrical specifications.
Specification
FAQ71BUV1B
FAQ100BUV1B
Heat exchanger
Rows x stages x fin pitch
2 x 16 x 1.4 mm
2 x 12 x 1.4 mm
Face area
0.289 m²
0.332 m²
Tube type
Hi-XA
N-Hix
Fin type
Multi louver
Fan
Air flow rate cooling (high)
19.0 m³/min
23.0 m³/min
Air flow rate cooling (low)
15.0 m³/min
19.0 m³/min
Air flow rate heating (high)
19.0 m³/min
23.0 m³/min
Air flow rate heating (low)
15.0 m³/min
19.0 m³/min
Qty x model (rotor)
1 x QCL9886M
1 x QCL
1 x QCL1163MB
Qty x model (motor)
1 x
(ARW30R8P43DA)
1 x D09P49A23
Fan speed
2 steps
Fan type
Cross flow fan
Refrigerant
Type
R410A
Safety and functional devices
Fan motor thermal
protector:
OFF: 130
+/- 5
°C
ON: 83
+/- 20
°C
Air filter
Resin net (mildew proof)
Temperature control
Microcomputer control
Weight
Unit
13 kg
26 kg
Specification
FAQ71BUV1B
FAQ100BUV1B
Unit
Phase
1~
Voltage
220-240 V
Frequency
50 Hz
Power consumption
68 W
101 W
Nominal running current
_
Fan motor
FLA (Full load amps)
0.4 A
No. of motors x output
1 x 43 W
1 x 49 W
Summary of Contents for FCQ35B7V1
Page 1: ...Service Manual ESIE05 04 R 410A Sky Air Indoor...
Page 2: ......
Page 20: ...ESIE05 04 1 2 Part 1 System Outline 3 1 1 5...
Page 62: ...General Outline ESIE05 04 1 44 Part 1 System Outline 3 1 1 4 5...
Page 78: ...ESIE05 04 1 60 Part 1 System Outline...
Page 112: ...Wiring Diagrams ESIE05 04 1 94 Part 1 System Outline 3 1 1 4 5...
Page 140: ...ESIE05 04 2 2 Part 2 Functional Description 3 1 2 5...
Page 164: ...ESIE05 04 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 206: ...Error Codes ESIE05 04 3 44 Part 3 Troubleshooting 3 1 3 4 5...
Page 224: ...Additional Checks for Troubleshooting ESIE05 04 3 62 Part 3 Troubleshooting 3 1 3 4 5...
Page 226: ...ESIE05 04 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 252: ...ESIE05 04 5 2 Part 5 Disassembly and Maintenance 3 1 5...
Page 384: ...Disassembly and Maintenance ESIE05 04 5 134 Part 5 Disassembly and Maintenance 3 1 5 5...
Page 390: ...ESIE05 04 vi Index 3 1 4 5 W Wiring diagrams Indoor units k 1 61...