Functional concept
ESIE05-04
2–20
Part 2 – Functional Description
3
1
2
4
5
1.15
Draft Avoidance Control 1
Purpose
Avoid draft for the customer by delaying transfer of the flap to the Po0 (horizontal) position for a certain
amount of time when defrosting and in heating thermostat OFF.
Heating thermostat
OFF
The time chart below illustrates the draft avoidance control 1 in heating thermostat OFF.
Defrosting
The time chart below illustrates the draft avoidance control 1 in defrosting.
Used inputs
The draft avoidance control 1 uses the following inputs:
When the flap starts to move, there can be
a draft. The fan speed decreases to LL
speed but it takes some time because of
its inertia.
Fan
Flap
Thermostat
Setting
LL
Setting
Po0
ON
OFF
Flap motor starts
to drive the flap.
20 s
Flap moves from
setting position to Po0
Po0
When the flap starts to move, there can be
a draft. The fan speed decreases to LL
speed but it takes some time because of
its inertia.
Fan
Flap
Defrosting
Setting
Off
Setting
Po0
Yes
No
Flap motor starts
to drive the flap.
20 s
Flap moves from
setting position to Po0
Po0
Input
Connection on
indoor PCB
Connection on
outdoor PCB
Limit switch for flap
33S
—
No. of fan turns
X26A
—
Outdoor heat exchanger thermistor (defrost control)
—
R2T
Summary of Contents for FCQ35B7V1
Page 1: ...Service Manual ESIE05 04 R 410A Sky Air Indoor...
Page 2: ......
Page 20: ...ESIE05 04 1 2 Part 1 System Outline 3 1 1 5...
Page 62: ...General Outline ESIE05 04 1 44 Part 1 System Outline 3 1 1 4 5...
Page 78: ...ESIE05 04 1 60 Part 1 System Outline...
Page 112: ...Wiring Diagrams ESIE05 04 1 94 Part 1 System Outline 3 1 1 4 5...
Page 140: ...ESIE05 04 2 2 Part 2 Functional Description 3 1 2 5...
Page 164: ...ESIE05 04 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 206: ...Error Codes ESIE05 04 3 44 Part 3 Troubleshooting 3 1 3 4 5...
Page 224: ...Additional Checks for Troubleshooting ESIE05 04 3 62 Part 3 Troubleshooting 3 1 3 4 5...
Page 226: ...ESIE05 04 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 252: ...ESIE05 04 5 2 Part 5 Disassembly and Maintenance 3 1 5...
Page 384: ...Disassembly and Maintenance ESIE05 04 5 134 Part 5 Disassembly and Maintenance 3 1 5 5...
Page 390: ...ESIE05 04 vi Index 3 1 4 5 W Wiring diagrams Indoor units k 1 61...