Test Run and Operation Data
ESIE05-04
4–24
Part 4 – Commissioning and Test Run
3
1
4
5
3.1
General Operation Data
Guide Lines for
Optimal Operation
Condition
The operation value guide lines when operating under standard conditions (at Rated frequency) by
pushing the test run button on the remote controller are as given in the table below.
Indoor Unit Fan:
“H” Operation Compressor: Rated Frequency
High
Pressure
(Mpa)
Low
Pressure
(Mpa)
Discharge
Pipe
Temperature
(°C)
Suction
Temperature
(°C)
Indoor Unit
Side:
Differential
Between
Suction Tem-
perature and
Discharge
Temperature
(°C)
Outdoor Unit
Side:
Differential
Between
Suction Tem-
perature and
Discharge
Temperature
(°C)
Cooling
26 bar ~
34 bar
6 bar ~
10 bar
60~100
–2~10
8~18
7~12
Heating
25 bar ~
32.6 bar
5.3 bar ~
9.5 bar
60~100
–6~2
14~30
2~6
Summary of Contents for FCQ35B7V1
Page 1: ...Service Manual ESIE05 04 R 410A Sky Air Indoor...
Page 2: ......
Page 20: ...ESIE05 04 1 2 Part 1 System Outline 3 1 1 5...
Page 62: ...General Outline ESIE05 04 1 44 Part 1 System Outline 3 1 1 4 5...
Page 78: ...ESIE05 04 1 60 Part 1 System Outline...
Page 112: ...Wiring Diagrams ESIE05 04 1 94 Part 1 System Outline 3 1 1 4 5...
Page 140: ...ESIE05 04 2 2 Part 2 Functional Description 3 1 2 5...
Page 164: ...ESIE05 04 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 206: ...Error Codes ESIE05 04 3 44 Part 3 Troubleshooting 3 1 3 4 5...
Page 224: ...Additional Checks for Troubleshooting ESIE05 04 3 62 Part 3 Troubleshooting 3 1 3 4 5...
Page 226: ...ESIE05 04 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 252: ...ESIE05 04 5 2 Part 5 Disassembly and Maintenance 3 1 5...
Page 384: ...Disassembly and Maintenance ESIE05 04 5 134 Part 5 Disassembly and Maintenance 3 1 5 5...
Page 390: ...ESIE05 04 vi Index 3 1 4 5 W Wiring diagrams Indoor units k 1 61...