Additional Checks for Troubleshooting
ESIE06-03
3–56
3
1
3
4
5
5.7
Discharge Pressure Check
Check No.08
Replace compessor.
Open the stop valve.
Replace the pipe installed at the
site.
Clean.
Replace the compressor.
YES
YES
YES
NO
NO
NO
NO
Discharge pressure check
Is the stop valve
open?
YES
High
Is the
connection pipe
deformed?
Are the
heat exchanger and
air filter dirty?