![background image](http://html.mh-extra.com/html/daikin/altherma-ekhbh-series/altherma-ekhbh-series_service-manual_501281017.webp)
ESIE06-03
Specifications
1–17
3
1
4
5
Electrical
specifications
The table below contains the electrical specifications.
Refrigerant oil
Type
FVC50K
Charged volume
0.75 l
Piping connections
Liquid
Type
Flare connection
Diameter (OD)
6.35 mm
Gas
Type
Flare connection
Diameter (OD)
15.9 mm
Drain Quantity
1
Type
Socket
Diameter (OD)
18 mm
Piping length
Min.
3 m
Max.
30 m
Equivalent
—
Chargeless
—
Additional refrigerant charge
0.02 IF > 10 m
Installation height difference max.
15 m
Max. interunit level difference
20 m
Defrost method
Reverse cycle
Defrost control
Sensor for outdoor heat exchanger temperature
Capacity control method
Inverter controlled
Standard accessories
Item
Installation manual, drain plug
Quantity
1
Specification
ERYQ005~007
Specification
ERYQ00
Power supply
Name
V1
Phase
1
Frequency
50 Hz
Voltage
220 V-240 V
Voltage range
Minimum
-10% (V)
Maximum
+10% (V)
Current
Nominal running current
Cooling
—
Heating
—
Starting current
Cooling
11 A
Heating
11 A
Maximum running current
Cooling
16.25 A
Heating
18 A
Recommended fuses
20 A
Wire connections
For power supply
Quantity
3
Remark
—
For connection with hydro-box
Quantity
4
Remark
Included earth wiring
Summary of Contents for Altherma EKHBH Series
Page 2: ...ESIE06 03 1 2 Part 1 System Outline 3 1 1 5 ...
Page 26: ...Functional Diagrams ESIE06 03 1 26 Part 1 System Outline 3 1 1 4 5 ...
Page 32: ...Piping Diagrams ESIE06 03 1 32 Part 1 System Outline 3 1 1 4 5 ...
Page 38: ...Switch Box Layout ESIE06 03 1 38 Part 1 System Outline 3 1 1 4 5 ...
Page 58: ...PCB Layout ESIE06 03 1 58 Part 1 System Outline 3 1 1 4 5 ...
Page 60: ...ESIE06 03 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 68: ...Hydro box Functional Concept ESIE06 03 2 10 Part 2 Functional Description 3 1 2 4 5 ...
Page 88: ...ESIE06 03 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 134: ...Error Codes System Malfunctions ESIE06 03 3 48 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 152: ...Additional Checks for Troubleshooting ESIE06 03 3 66 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 154: ...ESIE06 03 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...