Error Codes: Outdoor Units
ESIE06-03
3–34
3
1
3
4
5
Troubleshooting
See also:
P
P
P
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Replace the outdoor unit PCB.
Replace the fan motor.
Correct the connectors and fan
motor leads.
Replace the outdoor unit PCB.
Clean up the radiation fin.
YES
NO
Slightly dirty
Malfunctioning
Too dirty
Functioning
Error again or
outdoor unit fan activated?
C
heck No.
09
Check the outdoor unit
fan or related.
NO
YES
Above 95˚C?
Radiation fin dirty?
Turn off the power and turn it on
again.
Check the radiation fin temperature.
C
heck No.
07
Check the installation condition.
WARNING
To cool down the electricals, the
outdoor unit fan gets started when
the radiation fin temperature rises
above 95˚C and stops itself when it
drops below 80˚C.
Summary of Contents for Altherma EKHBH Series
Page 2: ...ESIE06 03 1 2 Part 1 System Outline 3 1 1 5 ...
Page 26: ...Functional Diagrams ESIE06 03 1 26 Part 1 System Outline 3 1 1 4 5 ...
Page 32: ...Piping Diagrams ESIE06 03 1 32 Part 1 System Outline 3 1 1 4 5 ...
Page 38: ...Switch Box Layout ESIE06 03 1 38 Part 1 System Outline 3 1 1 4 5 ...
Page 58: ...PCB Layout ESIE06 03 1 58 Part 1 System Outline 3 1 1 4 5 ...
Page 60: ...ESIE06 03 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 68: ...Hydro box Functional Concept ESIE06 03 2 10 Part 2 Functional Description 3 1 2 4 5 ...
Page 88: ...ESIE06 03 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 134: ...Error Codes System Malfunctions ESIE06 03 3 48 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 152: ...Additional Checks for Troubleshooting ESIE06 03 3 66 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 154: ...ESIE06 03 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...