Outdoor Unit Functional Concept
ESIE06-03
2–22
Part 2 – Functional Description
3
1
2
4
5
3.10
Low Hz High Pressure Limit
Outline
Heat Pump Only
Set the upper limit of high pressure in a low Hz zone. Set the upper limit of the indoor heat exchanger
temperature by its operating frequency of Hz. Separate into three zones, reset zone, unchanged zone
and drooping zone and the frequency control must be carried out in such zones.
Separate into zones
Note
Drooping: The system stops after staying in the drooping zone for 2 minutes.
Highest heat
exchanger
temperature
among the
operating rooms
Reset zone
60˚C
59˚C
56˚C
Unchanged
zone
Drooping zone
Summary of Contents for Altherma EKHBH Series
Page 2: ...ESIE06 03 1 2 Part 1 System Outline 3 1 1 5 ...
Page 26: ...Functional Diagrams ESIE06 03 1 26 Part 1 System Outline 3 1 1 4 5 ...
Page 32: ...Piping Diagrams ESIE06 03 1 32 Part 1 System Outline 3 1 1 4 5 ...
Page 38: ...Switch Box Layout ESIE06 03 1 38 Part 1 System Outline 3 1 1 4 5 ...
Page 58: ...PCB Layout ESIE06 03 1 58 Part 1 System Outline 3 1 1 4 5 ...
Page 60: ...ESIE06 03 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 68: ...Hydro box Functional Concept ESIE06 03 2 10 Part 2 Functional Description 3 1 2 4 5 ...
Page 88: ...ESIE06 03 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 134: ...Error Codes System Malfunctions ESIE06 03 3 48 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 152: ...Additional Checks for Troubleshooting ESIE06 03 3 66 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 154: ...ESIE06 03 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...