Error Codes: Outdoor Units
ESIE06-03
3–26
3
1
3
4
5
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
NO
Connection OK?
Connect properly.
Reactor connection check
Turn off the power
Compressor connection check
NO
Connection OK?
Connect properly.
YES
Reactor check
NO
10
Ω
or less?
Replace the reactor.
Replace the compressor or the
compressor relay harness.
Disconnect the compressor relay harness
from the outdoor unit PCB and measure
the resistance value between the terminals
of each 3 compressor with tester.
Disconnect the reactor from the outdoor
unit PCB and measure the resistance
value between reactor terminals with
tester.
Check the operation again and if
the error appears again, replace
the outdoor unit PCB.
YES
Compressor check
NO
YES
Between all each terminal
10
Ω
or less?
YES
Summary of Contents for Altherma EKHBH Series
Page 2: ...ESIE06 03 1 2 Part 1 System Outline 3 1 1 5 ...
Page 26: ...Functional Diagrams ESIE06 03 1 26 Part 1 System Outline 3 1 1 4 5 ...
Page 32: ...Piping Diagrams ESIE06 03 1 32 Part 1 System Outline 3 1 1 4 5 ...
Page 38: ...Switch Box Layout ESIE06 03 1 38 Part 1 System Outline 3 1 1 4 5 ...
Page 58: ...PCB Layout ESIE06 03 1 58 Part 1 System Outline 3 1 1 4 5 ...
Page 60: ...ESIE06 03 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 68: ...Hydro box Functional Concept ESIE06 03 2 10 Part 2 Functional Description 3 1 2 4 5 ...
Page 88: ...ESIE06 03 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 134: ...Error Codes System Malfunctions ESIE06 03 3 48 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 152: ...Additional Checks for Troubleshooting ESIE06 03 3 66 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 154: ...ESIE06 03 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...