ESIE06-03
Error Codes: Outdoor Units
3–27
3
3
4
5
1
3.11
“H6”
Compressor Startup Failure
Error code
H6
Method of
malfunction
detection
A compressor startup failure is detected by checking the compressor running condition through the
position detection circuit.
Malfunction
decision conditions
P
The compressor fails to start in about 15 seconds after the compressor run command signal is
sent.
P
Clearing condition: Continuous run for about 5 minutes (normal)
P
The system will be shut down if the error occurs 8 times.
Supposed causes
P
Compressor relay cable disconnected
P
Compressor itself defective
P
Outdoor unit PCB defective
P
Stop valve closed
P
Input voltage out of specification
Summary of Contents for Altherma EKHBH Series
Page 2: ...ESIE06 03 1 2 Part 1 System Outline 3 1 1 5 ...
Page 26: ...Functional Diagrams ESIE06 03 1 26 Part 1 System Outline 3 1 1 4 5 ...
Page 32: ...Piping Diagrams ESIE06 03 1 32 Part 1 System Outline 3 1 1 4 5 ...
Page 38: ...Switch Box Layout ESIE06 03 1 38 Part 1 System Outline 3 1 1 4 5 ...
Page 58: ...PCB Layout ESIE06 03 1 58 Part 1 System Outline 3 1 1 4 5 ...
Page 60: ...ESIE06 03 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 68: ...Hydro box Functional Concept ESIE06 03 2 10 Part 2 Functional Description 3 1 2 4 5 ...
Page 88: ...ESIE06 03 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 134: ...Error Codes System Malfunctions ESIE06 03 3 48 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 152: ...Additional Checks for Troubleshooting ESIE06 03 3 66 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 154: ...ESIE06 03 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...