Additional Checks for Troubleshooting
ESIE06-03
3–60
3
1
3
4
5
5.11
Capacitor Voltage Check
Check No.12
Before this checking, be sure to check the main circuit for short-circuit.
P
Checking the capacitor voltage
P
With the circuit breaker still on, measure the voltage according to the drawing of the model in
question. Be careful never to touch any live parts
OL lead wire
Thermistor lead wire
Fan motor lead wire
Electronic expansion valve
lead wire
Reversing solenoid
valve lead wire
(Heat pump type only)
Compressor lead wire
Reactor lead wire
Multimeter
(DC voltage range)
Summary of Contents for Altherma EKHBH Series
Page 2: ...ESIE06 03 1 2 Part 1 System Outline 3 1 1 5 ...
Page 26: ...Functional Diagrams ESIE06 03 1 26 Part 1 System Outline 3 1 1 4 5 ...
Page 32: ...Piping Diagrams ESIE06 03 1 32 Part 1 System Outline 3 1 1 4 5 ...
Page 38: ...Switch Box Layout ESIE06 03 1 38 Part 1 System Outline 3 1 1 4 5 ...
Page 58: ...PCB Layout ESIE06 03 1 58 Part 1 System Outline 3 1 1 4 5 ...
Page 60: ...ESIE06 03 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 68: ...Hydro box Functional Concept ESIE06 03 2 10 Part 2 Functional Description 3 1 2 4 5 ...
Page 88: ...ESIE06 03 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 134: ...Error Codes System Malfunctions ESIE06 03 3 48 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 152: ...Additional Checks for Troubleshooting ESIE06 03 3 66 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 154: ...ESIE06 03 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...