![background image](http://html.mh-extra.com/html/daikin/altherma-ekhbh-series/altherma-ekhbh-series_service-manual_501281136.webp)
Additional Checks for Troubleshooting
ESIE06-03
3–50
3
1
3
4
5
5.2
Fan Motor Connector Output Check
Check No.01
1
Check connector connection.
2
Check motor power supply voltage output (pins 4-7).
3
Check motor control voltage (pins 4-3).
4
Check rotation command voltage output (pins 4-2).
5
Check rotation pulse input (pins 4-1)
.
7
6
5
4
3
2
1
Motor power supply voltage
Unused
Unused
P.0V (reference potential)
Motor control voltage (15 VDC)
Rotation command voltage (1~ 6 VDC)
Rotation pulse input