Error Codes: Outdoor Units
ESIE06-03
3–38
3
1
3
4
5
Troubleshooting 1
An output over-current may result from wrong internal wiring. If the wires have been disconnected and
reconnected for part replacement, for example, and the system is interrupted by an output
over-current, take the following procedure:
Replace the compressor.
Correct the power supply.
Replace the PM1.
(Replace the outdoor unit
PCB.)
Correct the power supply or
replace the PM1.
(Replace the outdoor unit
PCB.)
Check the electricals'
connectors and other
fittings.
∗
Inverter checker
Part No.: 1225477
Keep on using as it is
(monitor).
Fully open the stop valve.
NO
YES
NO
YES
Stop valve fully open?
Error again?
NO
YES
Voltage as rated?
YES
NO
Short-circuit
or breakage between
compressor's coil
phases?
NO
YES
Normal?
YES
NO
Any LED off?
Turn off the power and turn it on
again to get the system started.
See if the same error occurs.
Turn off the power and disconnect
the harnesses U, V and W.
Check with the inverter checker (*)
Monitor the supply voltage,
discharge and suction pressures,
and other factors for a long term.
Possible causes
•
Instantaneous supply voltage
drop
•
Compressor motor overloaded
•
Contact-induced electrical short-
circuit
Turn off the power, and reconnect the
harnesses. Turn on the power again and
get restarted.
Check the supply voltage.
C
heck No.
13
Check the power transistor.
Check No. 08
Check the discharge pressure.
Check No. 07
Check the installation condition.
Summary of Contents for Altherma EKHBH Series
Page 2: ...ESIE06 03 1 2 Part 1 System Outline 3 1 1 5 ...
Page 26: ...Functional Diagrams ESIE06 03 1 26 Part 1 System Outline 3 1 1 4 5 ...
Page 32: ...Piping Diagrams ESIE06 03 1 32 Part 1 System Outline 3 1 1 4 5 ...
Page 38: ...Switch Box Layout ESIE06 03 1 38 Part 1 System Outline 3 1 1 4 5 ...
Page 58: ...PCB Layout ESIE06 03 1 58 Part 1 System Outline 3 1 1 4 5 ...
Page 60: ...ESIE06 03 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 68: ...Hydro box Functional Concept ESIE06 03 2 10 Part 2 Functional Description 3 1 2 4 5 ...
Page 88: ...ESIE06 03 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 134: ...Error Codes System Malfunctions ESIE06 03 3 48 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 152: ...Additional Checks for Troubleshooting ESIE06 03 3 66 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 154: ...ESIE06 03 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...