Error Codes: Outdoor Units
3–23
3
3
4
5
1
3.9
“F6”
High Pressure Control in Cooling
Error code
F6
Method of
malfunction
detection
High-pressure control (stop, frequency drop, etc.) is activated in the cooling mode if the temperature
being sensed by the heat exchanger thermistor exceeds the limit.
Malfunction
decision conditions
Activated when the temperature being sensed by the heat exchanger thermistor rises above 60°C.
(Deactivated when the said temperature drops below 50°C)
Supposed causes
P
The installation space is not large enough.
P
Faulty outdoor unit fan
P
Faulty electronic expansion valve
P
Faulty defrost thermistor
P
Faulty outdoor unit PCB
P
Faulty stop valve
P
Dirty heat exchanger
Summary of Contents for Altherma EKHBH Series
Page 2: ...ESIE06 03 1 2 Part 1 System Outline 3 1 1 5 ...
Page 26: ...Functional Diagrams ESIE06 03 1 26 Part 1 System Outline 3 1 1 4 5 ...
Page 32: ...Piping Diagrams ESIE06 03 1 32 Part 1 System Outline 3 1 1 4 5 ...
Page 38: ...Switch Box Layout ESIE06 03 1 38 Part 1 System Outline 3 1 1 4 5 ...
Page 58: ...PCB Layout ESIE06 03 1 58 Part 1 System Outline 3 1 1 4 5 ...
Page 60: ...ESIE06 03 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 68: ...Hydro box Functional Concept ESIE06 03 2 10 Part 2 Functional Description 3 1 2 4 5 ...
Page 88: ...ESIE06 03 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 134: ...Error Codes System Malfunctions ESIE06 03 3 48 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 152: ...Additional Checks for Troubleshooting ESIE06 03 3 66 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 154: ...ESIE06 03 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...