background image

Cancels: New

II 619E-18-4

4/1/06

installation, start-up and
service instructions

FAN COIL UNITS

619ENF

619ENQ

Sizes 018-036

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . . . . .  1

GENERAL

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  1

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-13

I.  Step 1 — Complete Pre-Installation Checks

. . . . . .  1

II.  Step 2 — Mount Unit

 . . . . . . . . . . . . . . . . . . . . . . . . .  5

III.  Step 3 — Complete Refrigerant Piping 

Connections

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5

IV.  Step 4 — Make Electrical Connections

 . . . . . . . . . .  8

START-UP

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  13

SERVICE

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  14

TROUBLESHOOTING

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 14,15

SAFETY CONSIDERATIONS

Installing and servicing air-conditioning equipment can be

hazardous due to system pressure and electrical components.

Only trained and qualified service personnel should install or

service air-conditioning equipment.
Untrained personnel can perform basic maintenance, such as

cleaning and replacing filters. All other operations should be

performed by trained service personnel. When working on air

conditioning equipment, observe safety precautions in litera-

ture, tags, and labels attached to unit.
Follow all safety codes. Wear safety glasses and work gloves.

Use quenching cloth for brazing operations. Have fire extin-

guisher available. Read these instructions 

thoroughly

. Con-

sult local building codes and the National Electrical Code

(NEC) for special installation requirements.

GENERAL

These instructions cover the installation, start-up and service

of cooling only and heat pump duct-free systems.

INSTALLATION

I. STEP 1 — COMPLETE PRE-INSTALLATION CHECKS

A. Unpack Units (See Fig. 1)

Move the unit to final location. Remove unit from carton,

being careful not to damage service valves and grilles. See

Table 1A for installation materials included in shipment and

see Table 1B for field supplied materials needed to complete

the installation.

B. Inspect Shipment

File a claim with the shipping company if shipment is dam-

aged or incomplete. Check the unit nameplate to ensure unit

matches the job requirements.

C. Consider System Requirements

Consult local building codes and NEC for special installation

requirements. Use only designated indoor units with outdoor

units. See Tables 2 and 3.

WARNING: 

 

Before installing or servicing system,

always turn off main power to system. There may be

more than one disconnect switch. Turn off accessory

heater power if applicable. Electrical shock can cause

serious personal injury.

CAUTION: 

 

This system uses R-410A, which has

higher pressures than R-22 and other refrigerants. No

other refrigerant may be used  in  this  system.  All

equipment must be designed to handle R-410A refrig-

erant. If unsure about equipment, consult the equip-

ment manufacturer.

Fig. 1 — 619ENF,ENQ Units

Summary of Contents for 619ENF

Page 1: ...EC for special installation requirements GENERAL These instructions cover the installation start up and service of cooling only and heat pump duct free systems INSTALLATION I STEP 1 COMPLETE PRE INSTALLATION CHECKS A Unpack Units See Fig 1 Move the unit to final location Remove unit from carton being careful not to damage service valves and grilles See Table 1A for installation materials included ...

Page 2: ...eless Remote Control Mounting Bracket 1 For wireless remote control installation NAME SPECIFICATIONS Connection Pipe nominal capacity Liquid line 3 8 in 619ENF ENQ018 036 Mixed Phase line 5 8 in 619ENF01824 and 619ENQ018 024 3 4 in 619ENF ENQ030 036 Wall Sleeve Wall Cap Finishing Tape PVC Film Fastening Tape Pipe Insulation Drain Hose 5 8 in 619ENF01824 and 619ENQ018 024 3 4 in 619ENF ENQ030 036 S...

Page 3: ... 619ENF ENQ 16 16 16 20 18 18 18 18 Circuits 5 5 9 9 FILTERS Quantity Size in 2 12 5 x 16 1 2 12 5 x 16 1 3 17 3 x 16 1 3 17 3 x 16 1 AIR SWEEP Horizontal Manual Manual Automatic Automatic Vertical Automatic Automatic Automatic Automatic OPERATING LIMITS Heating Min Max 81 F db Cooling Min Max 59 F wb 70 F db 74 F wb 90 F db CONTROLS Integrated Microprocessor Remote Controller Options Wireless CRC...

Page 4: ...in min min 4 in 4 in 80 in 8 in Fig 2 Unit Dimensions 619ENF01824 619ENQ018 024 DIMENSIONS in 619ENF ENQ 030 036 DIMENSIONS in A 42 5 57 5 B 11 6 13 4 C 7 9 9 5 619ENF ENQ 619ENF ENQ UNITS Fig 3 Unit Clearances ...

Page 5: ...P 3 COMPLETE REFRIGERANT PIPING CONNECTIONS When running the piping for indoor units the piping can be con nected as rear piping or side or bottom piping Refer to Fig 4 A Rear Piping Route the piping behind the indoor unit so that the piping is concealed by the unit For rear piping installation drill a 21 2 in diameter hole in the wall at point A or B in Fig 6 Drill the hole at a slope so that the...

Page 6: ... line sizes Do not use less than 10 ft of interconnecting tubing If either refrigerant tubing or indoor coil is exposed to the atmosphere the system must be evacuated following good refrigeration practices Run refrigerant tubes as directly as possible avoiding unnecessary turns and bends Suspend refrigerant tubes so they do not damage insulation on vapor tube and do not transmit vibration to struc...

Page 7: ...Do not use the unit refrigerant gas to purge the connecting pipes Remove the caps from the valves Create a vacuum with a vacuum pump connected to the service connection of the suc tion shut off valves completely shut until a 50 Pa vacuum has been reached Open the mixed phase valve for 3 seconds then quickly shut it to check for possible leaks Replace caps and check for leaks using a leak detector ...

Page 8: ...e possibility of personal injury if an electrical fault should occur This ground may consist of electrical wire connected to unit ground lug in control compart ment or conduit approved for electrical ground when installed in accordance with NEC and local electrical codes Failure to follow this warning could result in the installer being liable for the personal injury of others CAUTION Unit failure...

Page 9: ... 9 Fig 16 619ENF01824 Matched with 538ENF Typical Wiring Schematic ...

Page 10: ... 10 Fig 17 619ENQ018 024 Matched with 538QNF Typical Wiring Schematic ...

Page 11: ... 11 Fig 18 619ENF030 036 Matched with 538ENF Typical Wiring Schematic ...

Page 12: ... 12 Fig 19 619ENQ030 036 Matched with 538QNF Typical Wiring Schematic ...

Page 13: ...re being installed in the same room working independently two remote controls need to be con figured for proper operation A Unit Configuration Turn the unit off by pressing the Press and hold the and buttons of the remote control for more than 5 seconds The display will be cleared and the time segments will display the first configuration item rAdr remote address and the temperature segments will ...

Page 14: ...t in operation the green LED on the indoor unit flashes at intervals of 0 5 sec onds The fault code is deduced from the number of times the green LED flashes blocking unit operation Between one flash cycle and the next one a pause of 3 seconds elapses Table 6 Green LED Indoor Unit Fault WARNING Before performing recommended maintenance be sure unit main power switch is turned off Failure to do so ...

Page 15: ...on Indoor temperature setting too low or too high Check temperature setting Outdoor unit fan faulty Replace outdoor fan Air or other noncondensable gasses in the circuit Drain refrigerant evacuate and recharge CAUTION Do not vent refrigerant to the atmosphere use refrigerant recovery equipment Obstructions at air intake or dirty indoor unit filters Remove obstruction and or clean filter Frequent I...

Page 16: ...Copyright 2006 Bryant Heating Cooling Systems Printed in U S A CATALOG NO 02 619E0001 SI ...

Reviews: