Thermistor Resistance Check
Check No.06
Remove the connectors of the thermistors on the PCB, and measure the resistance of each thermistor
using tester.
The relationship between normal temperature and resistance is shown in the graph and the table
below:
Hydro-box
Tank thermistor
3SA48002
3SA48009
R25°C=20k
Ω
R120=7.13
Ω
B=3990
B= 4177
-20
197.8 k
Ω
2534 k
Ω
-15
148.2 k
Ω
1877 k
Ω
-10
112.0 k
Ω
1404 k
Ω
-5
85.52 k
Ω
1059 k
Ω
0
65.84 k
Ω
806.5 k
Ω
5
51.05 k
Ω
618.9 k
Ω
10
39.91 k
Ω
478.8 k
Ω
15
31.44 k
Ω
373.1 k
Ω
20
24.95 k
Ω
292.9 k
Ω
25
19.94 k
Ω
231.4 k
Ω
30
16.04 k
Ω
184.1 k
Ω
35
12.99 k
Ω
147.4 k
Ω
40
10.58 k
Ω
118.7 k
Ω
45
8.669 k
Ω
96.13 k
Ω
50
7.143 k
Ω
78.29 k
Ω
Summary of Contents for Altherma EKHBH Series
Page 2: ...ESIE06 03 1 2 Part 1 System Outline 3 1 1 5 ...
Page 26: ...Functional Diagrams ESIE06 03 1 26 Part 1 System Outline 3 1 1 4 5 ...
Page 32: ...Piping Diagrams ESIE06 03 1 32 Part 1 System Outline 3 1 1 4 5 ...
Page 38: ...Switch Box Layout ESIE06 03 1 38 Part 1 System Outline 3 1 1 4 5 ...
Page 58: ...PCB Layout ESIE06 03 1 58 Part 1 System Outline 3 1 1 4 5 ...
Page 60: ...ESIE06 03 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 68: ...Hydro box Functional Concept ESIE06 03 2 10 Part 2 Functional Description 3 1 2 4 5 ...
Page 88: ...ESIE06 03 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 134: ...Error Codes System Malfunctions ESIE06 03 3 48 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 152: ...Additional Checks for Troubleshooting ESIE06 03 3 66 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 154: ...ESIE06 03 5 2 Part 5 Disassembly and Maintenance 3 1 5 ...