Troubleshooting for SA Indoor Unit - FFQ Series
SiBE12-816_D
225
Service Diagnosis
Troubleshooting
Note:
If "
A3
" is detected by the indoor unit PCB which is not mounted with X15A, the indoor unit PCB
is defective.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Connect the drain pump.
Replace the indoor unit
PCB.
Replace the drain pump.
There is a drain system
abnormality.
Connect the float switch.
Replace the float switch.
Replace the indoor unit
PCB.
(R11295)
NO
YES
NO
NO
YES
YES
Is the drain
pump connected to the
indoor unit PCB?
NO
Is the drain water level
abnormally high?
YES
YES
Is the float switch
connected to X15A?
NO
Does
the drain pump work after
restarting operation?
YES
Remove the float switch from
X15A, short circuit X15A, and
restart operation.
NO
Does
"
A3
" appear on the remote
controller display?
Set to
"emergency" and check
the voltage of X25A.
220 VAC?