Troubleshooting for Outdoor Unit
SiBE12-816_D
241
Service Diagnosis
7.6
Discharge Pipe Temperature Control
Remote
Controller
Display
F3
Method of
Malfunction
Detection
Detected by the discharge pipe thermistor
Malfunction
Decision
Conditions
If the temperature detected by the discharge pipe thermistor rises above
A
°C, the
compressor stops.
The error is cleared when the discharge pipe temperature is dropped below
B
°C.
If the error repeats 4 times, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Refrigerant shortage
Defective four way valve
Defective discharge pipe thermistor
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Defective outdoor unit PCB
Water mixed in refrigerant
Defective electronic expansion valve
Defective stop valve
Troubleshooting
Check No.01
Refer to P.261
Check No.12
Refer to P.263
Check No.14
Refer to P.265
A
(°C)
B
(°C)
40 class
110
97
50 class
110
95
(R14412)
Caution
NG
OK
OK
OK
NG
NG
•
Discharge pipe thermistor
•
Outdoor heat exchanger thermistor
•
Outdoor temperature thermistor
•
Refrigerant shortage
•
Four way valve
•
Water mixed
•
Stop valve
Check No. 01
Check the thermistors.
Check No. 14
Check the refrigerant
line.
Check No. 12
Check the electronic
expansion valve.
Replace the
defective
thermistor.
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.