SiBE12-816_D
Field Settings
Trial Operation and Field Settings
304
FTXS-G, FTXS-J Series
< Floor Standing Type>
1) Remove the front grille.
2) Lift the sensor PCB fixing plate and remove the front shield plate.
3) Disconnect the connectors [S1] [S41] [S42].
4) Remove the electric box (1 screw).
5) Pull out the indoor heat exchanger thermistor.
6) Remove the shield plate (8 tabs).
7) Cut the address setting jumper JA on the indoor unit PCB.
8) Cut the address setting jumper in the remote controller.
(Refer to “Wireless remote controller”.)
ADDRESS
JA
ADDRESS
JA
EXIST
1
CUT
2
(R12216)
3) Connector [S42]
3) Connector [S41]
3) Connector [S1]
4) Remove the screw.
5) Indoor heat exchanger
thermistor
JA
Address
EXIST
1
CUT
2
JA
JC
JB
2) Front shield plate
6) Shield plate
2)
(R11692)
Sensor
PCB fixing
plate