Forced Cooling Operation
SiBE12-816_D
299
Trial Operation and Field Settings
2. Forced Cooling Operation
ex. Wall mounted type FTXS Series
Item
Forced Cooling
Conditions
The forced cooling operation is allowed when both the following conditions
are met.
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
Start
Press the forced cooling operation ON/OFF button (SW1) on the indoor unit
for 5 seconds.
Operating room
All rooms
Command frequency
40 class: 70 Hz
50 class: 47 Hz
End
The forced cooling operation ends when any of the following conditions is
fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation ON/OFF button (SW1) on the indoor
unit again.
Others
The protection functions are prior to all others in the forced cooling
operation.
(R14226)
ON/OFF button (SW1)