ENGLISH
103
6.6.14.1 O1: Output 1 function setting
Output 1 notifies of an active alarm (i.e. that there is a system block). The output enables use of a normally
closed or normally open voltage-free contact.
Parameter O1 is associated with the values and functions specified in Table 26.
6.6.14.2 O2: Output 2 function setting
Output 2 notifies of electric pump running status (pump on/off). The output enables use of a normally closed
or normally open voltage-free contact.
Parameter O2 is associated with the values and functions specified in Table 26.
Configuration of functions associated with outputs
Output
configuration
OUT1
OUT2
Activation
conditions
Output contact
status
Activation
conditions
Output contact
status
0
No function
associated
NO contact always open,
NC contact always closed
No function
associated
NO contact always open,
NC contact always closed
1
No function
associated
NO contact always
closed, NC contact always
open
No function
associated
NO contact always
closed, NC contact always
open
2
Presence of blocking
errors
In event of blocking errors
NO contact closes and
NC contact opens
Activation of output in
event of blocking
errors
When the pump is
running, the NO contact
closes and the NC contact
opens
3
Presence of blocking
errors
In event of blocking errors
NO contact opens and NC
contact closes
Activation of output in
event of blocking
errors
When the pump is
running, the NO contact
opens and the NC contact
closes
Table 26: Output configuration
6.6.15 RF: Fault and warning log reset
To clear the fault and warning log, press and hold the b and – simultaneously for at least 2 seconds.
The number of faults present in the log (max. 64) are summarised below the RF symbol.
The log can be viewed from the MONITOR menu on the FF page.
Summary of Contents for MCE-55/P
Page 278: ...274 1 276 2 279 3 280 4 282 5 283 6 4 20 284 7 285 8 286 9 287 10 290 11 290 12 292...
Page 279: ...275 IEC 60634...
Page 280: ...276 1 6 MCE 55 P e MCE 30 P 1 1 1...
Page 282: ...278 2 5 2 1 2 1 2 2 1 1 2 1 2 L L L 2 2 4 15...
Page 283: ...279 2 2 2 1 2 2 1 1 4 3 1 RST 2 2 4 3 1 8 3 3...
Page 284: ...280 AS 3 3 2 2 1 2 4 3 1 UVW 4 2 4 3 50 60 200 1...
Page 286: ...282 4 2 2 3 Press e Flow 5 A B C D d1 d2...
Page 291: ...287 3 9 64 X 128 4 MODE SET 10 7 MODE 1 SET 7 3 EEprom SET 6 SET MODE...
Page 292: ...288 3 1 9 3 2 1 2 3 2 1 MODE SET MODE 8 2 2 5 5 5 2 2 8...
Page 294: ...290 3 2 2 11 SET 10 15 12 11...
Page 296: ...292 12 11 13 GO SB...
Page 297: ...293 4 4 1 Link 8 4 2 4 2 1 Link 2 Link 5...
Page 300: ...296 4 3 1 2 1 4 3 1 3 SET MODE LA RC FN MS FS FL AC AE O1 1 O2 2 4 4 ET 6 6 9 FL...
Page 326: ...322 BL 10 6 24 24 30 LP 295 348 HP OT TE 100 C 85 C OB BT 120 C 100 C OC 10 6 OF 10 6 29...
Page 327: ...323 8 8 1 PMW 4 2 8 2 8 3 8 3 SET EE EEprom FLASH...
Page 494: ...490 1 492 2 495 3 496 4 498 5 499 6 4 20 mA 500 7 501 8 502 9 503 10 506 11 506 12 508 13 523...
Page 495: ...491 IEC 364 inverter...
Page 496: ...492 1 Inverter inverter inverter 6 inverter MCE 55 P MCE 30 P 1 1 1...
Page 502: ...498 4 2 2 3 Press Flow 5 A B C D d1 d2...
Page 507: ...503 3 9 oled 64 X 128 4 MODE SET 9 inverter 7 MODE 1 SET 7 3 EEprom SET 6 SET MODE...
Page 508: ...504 3 1 9 3 2 1 2 3 2 1 MODE SET Setpoint MODE 8 ONOMA TOY MENOY 2 Setpoint 2 5 5 5 2 2 8...
Page 512: ...508 12 11 12 GO SB FAULT...
Page 543: ...539 8 8 1 PMW 4 2 8 2 inverter 8 3 8 3 inverter SET EEPROM FLASH setpoint...
Page 599: ...595...