![DAB MCE-55/P Instruction For Installation And Maintenance Download Page 105](http://html1.mh-extra.com/html/dab/mce-55-p/mce-55-p_instruction-for-installation-and-maintenance_3147946105.webp)
ENGLISH
101
When in the F1 error condition, the input must be deactivated for at least 30 seconds before the system
unblocks. The function behaviour is summarised in Table 21.
When several float functions are configured at the same time on different inputs, the system indicates F1
when at least one function is activated and clears the alarm when none are activated.
Behaviour of external float function
Signal on terminal
Input
configuration
Operation
Item on display
Input not energised
1 (NO)
Normal
None
Input energised
1 (NC)
System block due to water failure
from external float
F1
Input not energised
2 (NO)
System block due to water failure
from external float
F1
Input energised
2 (NC)
Normal
None
Table 21: External float function
6.6.13.3 Setting the auxiliary pressure input function
The auxiliary pressure function modifies the system setpoint from pressure SP (see section 6.3) to pressure
Pi (see Impostazione funzione ingresso pressione ausiliaria section 6.6.13.3) where "i” represents the input
used. In this way, as well as SP, there are further four pressure values available (P1, P2, P3, P4).
When this function is enabled, the symbol Pi is shown on the STATUS line of the main page.
The input must be active for at least 1 second for the system to operate with the auxiliary setpoint.
When operating with the auxiliary setpoint, the input must not be active for at least 1 second to return to
operation with setpoint SP. The function behaviour is summarised in Table 22.
If several auxiliary pressure values are configured at the same time on different inputs, the system indicates
Pi when at least one function is activated. For simultaneous activations, the pressure reached will be the
lowest from those with the input active. The alarm is cleared when no input is activated.
Behaviour of auxiliary pressure function
Signal on terminal
Input
configuration
Operation
Item on display
Input not energised
3 (NO)
Auxiliary setpoint not active
None
Input energised
3 (NC)
Auxiliary setpoint active
Pi
Input not energised
4 (NO)
Auxiliary setpoint active
Pi
Input energised
4 (NC)
Auxiliary setpoint not active
None
Table 22: Auxiliary setpoints
6.6.13.4 Setting the system enable and fault reset
When this function is active, the system is totally disabled, and F3 is displayed n the STATUS line of the
main page.
When several system disable functions are configured at the same time on different inputs, the system
indicates F3 when at least one function is activated and clears the alarm when none are activated.
The input must be active for at least 1 second for the system to implement the disable function.
When the system is disabled, the input must not be active for at least 1 second for the function to be
deactivated (system re-enable). The function behaviour is summarised in Table 23.
If several disable functions are configured at the same time on different inputs, the system indicates F3 when
at least one function is activated. The alarm is cleared when no input is activated.
Summary of Contents for MCE-55/P
Page 278: ...274 1 276 2 279 3 280 4 282 5 283 6 4 20 284 7 285 8 286 9 287 10 290 11 290 12 292...
Page 279: ...275 IEC 60634...
Page 280: ...276 1 6 MCE 55 P e MCE 30 P 1 1 1...
Page 282: ...278 2 5 2 1 2 1 2 2 1 1 2 1 2 L L L 2 2 4 15...
Page 283: ...279 2 2 2 1 2 2 1 1 4 3 1 RST 2 2 4 3 1 8 3 3...
Page 284: ...280 AS 3 3 2 2 1 2 4 3 1 UVW 4 2 4 3 50 60 200 1...
Page 286: ...282 4 2 2 3 Press e Flow 5 A B C D d1 d2...
Page 291: ...287 3 9 64 X 128 4 MODE SET 10 7 MODE 1 SET 7 3 EEprom SET 6 SET MODE...
Page 292: ...288 3 1 9 3 2 1 2 3 2 1 MODE SET MODE 8 2 2 5 5 5 2 2 8...
Page 294: ...290 3 2 2 11 SET 10 15 12 11...
Page 296: ...292 12 11 13 GO SB...
Page 297: ...293 4 4 1 Link 8 4 2 4 2 1 Link 2 Link 5...
Page 300: ...296 4 3 1 2 1 4 3 1 3 SET MODE LA RC FN MS FS FL AC AE O1 1 O2 2 4 4 ET 6 6 9 FL...
Page 326: ...322 BL 10 6 24 24 30 LP 295 348 HP OT TE 100 C 85 C OB BT 120 C 100 C OC 10 6 OF 10 6 29...
Page 327: ...323 8 8 1 PMW 4 2 8 2 8 3 8 3 SET EE EEprom FLASH...
Page 494: ...490 1 492 2 495 3 496 4 498 5 499 6 4 20 mA 500 7 501 8 502 9 503 10 506 11 506 12 508 13 523...
Page 495: ...491 IEC 364 inverter...
Page 496: ...492 1 Inverter inverter inverter 6 inverter MCE 55 P MCE 30 P 1 1 1...
Page 502: ...498 4 2 2 3 Press Flow 5 A B C D d1 d2...
Page 507: ...503 3 9 oled 64 X 128 4 MODE SET 9 inverter 7 MODE 1 SET 7 3 EEprom SET 6 SET MODE...
Page 508: ...504 3 1 9 3 2 1 2 3 2 1 MODE SET Setpoint MODE 8 ONOMA TOY MENOY 2 Setpoint 2 5 5 5 2 2 8...
Page 512: ...508 12 11 12 GO SB FAULT...
Page 543: ...539 8 8 1 PMW 4 2 8 2 inverter 8 3 8 3 inverter SET EEPROM FLASH setpoint...
Page 599: ...595...