41
EXPERT 64+, rev.12
EXPERT 64+
Opening of the Curtain as
a Function of Static Pressure
Time
Static
Pressure
The
curtain open
The
curtain close
Sidewall
Lo pressure
limits*
Sidewall
Hi pressure
limits*
The curtain
starts closing
after the Wind
Delay has
elapsed.
The curtain
start opening
after the Wind
Delay has
elapsed.
The curtain
stop closing
The curtain
stop opening
Wind
Delay
Wind
Delay
The
curtain do not move
*The Hi and Lo pressure limits can automatically be adjusted according to the outside temperature
6.3.2.2. Curtain Settings
1. Select:
»
6. Inlet Settings
»
3. Tunnel Curtain
2. Set the following parameters:
(Refer to the previous section to get further informa-
tion on these parameters)
Minimum Outside Temperature —
This is the
outside temperature below which the tunnel
curtain remains closed. Adjustable from 0.1
to 100°F (-17.7 to 37.8°C). Select
“Off”
to
deactivate this function. *
Available if an outside
temperature probe is enabled (sec. 4.5.1)
Minimum Age —
This is the animal age below
which the tunnel curtain remains closed.
Adjustable from 1 to 450 days.
Curtain Starts Opening at Tunnel Fan Group
#x —
The tunnel curtain starts opening at the
start-up of this tunnel fan group.