49
EXPERT 64+, rev.12
EXPERT 64+
6.6. Stir Fans
The controller has one stir fan output that
can either operate during minimum ventilation
cycles or when the room temperature falls
below a user-defined limit.
• Based on the room temperature:
When they are based on the room tempera-
ture, stir fans start running in timer mode
when the room temperature falls below
their Start Temperature; they return to a
stop when the room temperature increases
and reaches the output’s stop temperature.
These Start & Stop Temperatures are related
to the house set point which means they are
automatically adjusted when changes occur
to the set point.
Operating Diagram
of a Stir Fan based on
the House T°
House T°
Stir Fan
Status
On
Off
Start T°
Stop T°
The stir fan timer is composed of an On Time
and of a Cycle Time as illustrated.
ON
OFF
Output
Status
Stir Fan Timer
Time
ON Time
Cycle
Time
• Based on the minimum ventilation:
When they are based on minimum ventilation,
stir fans are activated during every minimum
ventilation cycle’s Off Time. This ensures a
good air circulation when the fans are not
running.
1. Select
»
8. ON / OFF Temperature
»
2. Stir Fans*
* This menu is accessible if the stir fan output is
enabled (sec. 4.4).
2. Set the following parameters:
Stir Fan Settings
Operation based on
Temper.
ON
76.0 °F
OFF
77.0 °F
On Time
0:30 (m:s)
Cycle Time
5:00 (m:s)
Operation based on —
Select the proper oper-
ating mode of the stir fan output: temperature
or minimum ventilation.
ON / OFF Temperatures —
Set the start and
stop temperatures of the stir fan output.
*
Accessible it the stir fans’ operation is based on
the temperature.
ON / Cycle Times —
Set the On and Off times
of the stir fan timer to the desired value.
*
Accessible it the stir fans’ operation is based on
the temperature.