13
EXPERT 64+, rev.12
EXPERT 64+
4.4. Installation Setup
The following section shows how to cus-
tomize the controller for your particular
application. It shows how to enable and set
the outputs of your controller. Normally, this
setup needs to be done only once.
Hint: A worksheet is available at the
end of this manual to write down your
Installation Setup parameters.
1. Select:
»
12. Setup
»
4. Installation*
* This menu is only accessible from the installer
mode (sec. 4.2).
2. Set the following parameters:
Number of Programs —
The controller can use
several temperature programs. Enable the de-
sired number of programs (1 to 5 programs)
*
This parameter is common to all programs of the
controller.
Number of Temperature Probes —
Select the
number of inside temperature probes that are
connected to the controller (1 to 8 probes).
*
This parameter is common to all programs of the
controller.
Number of Heaters —
Enable the proper
number of heating outputs (0 to 8 outputs).
*
Refer to the “Hi Fire” option below to increase the
number of heating outputs.
Number of Fans —
Enable the proper number
of fan groups (1 to 5 groups).
Number of Tunnel Fans —
Enable the proper
number of tunnel fan groups (from 0 to
16 groups).
Use Stir Fans ? —
Select
“Yes”
to use the stir
fan output.
Number of Cooling —
Enable the proper num-
ber of cooling outputs (0 to 6 outputs).
Number of Clocks —
Enable the proper num-
ber of clock outputs. Adjustable from 0 to
12 outputs.
Number of Light Programs —
Enable the
proper number of light programs (0 to 10 pro-
grams. *
This parameter is common to all programs
of the controller.
Clock Outputs’ Operation Mode —
The clock
mode allows stopping a clock output at a
certain time of the day or after a certain run
time. Select “
Start/Stop”
to specify the time at
which each cycle starts and stops or select
“Start/Run”
to specify the running time of each
cycle. Note that the
“Start/Run”
option allows
stopping cycles with more precision since this
mode allows adjusting the seconds. Refer to
chapter 9 for further information about the
clock outputs. *
This parameter is common to all
programs of the controller.
Use Heater Lo/Hi Fire? —
Select
“Yes”
to acti-
vate the heating outputs’ Lo & Hi fire option.
This function allows doubling the number of
heating outputs.
Exit: Press Back
Change: Press Modify
Press
to select an item
Installation
Number of Programs
3
Number of Probes
8
Number of Heaters
4
Number of Fans
3
Number of Tunnel Fans
8
Use Stir Fans ?
Yes
Number of Cooling
6
Number of Clock
2
Number of Light Programs
2
Clock Mode
Start/Stop
Use Heater Lo / Hi Fire?
Yes
Use Day / Night OnTime?
Yes
Number of Vent Doors?
2
Use Attic Probe ?
Yes
Use Tunnel Curtain?
Yes
Curtain Control
SP
Number of relays
32
Monitor Breaker Temperature?
Yes
Show On Digit Display
T°/SP