6. VENTILATION SETTINGS
6.1.
Minimum Ventilation
6.1.1. Principle of Operation
Definition:
Minimum ventilation cycles are
activated when the room temperature is
lower than the start temperature of the first
fan/tunnel fan group. Running the fans even
though ventilation is not required for reduc-
ing the room temperature is useful to reduce
humidity levels and supply oxygen to the
room. It also prevents the fans from freezing
in winter.
Minimum Ventilation Timer:
The minimum
ventilation timer is composed of an
“On Time”
and of a
“Cycle Time”
. The fans run during
the
“On Time”
and then stop until the end of
the
“Cycle Time”
. This timer is common to all
programs of the controller.
Min.Vent
Fan Status
ON
OFF
Time
ON Time
Cycle Time
Minimum
Ventilation Timer
Minimum ventilation parameters are com-
mon to all programs of the controller.
The controller can extract the warm air
from the attic by increasing the operating
time of the fans in minimum ventilation.
Refer to section 6.4.3 for further infor-
mation about this feature.
1. Select:
»
5. Minimum Ventilation Timer
Minimum Ventilation Timer
On Time
1:30 (m:s)
Cycle Time
5:00 (m:s)
2. Set the following parameters:
On Time —
The fans’ operation time, within
the minimum ventilation cycles, can be ad-
justed from 0 to 5 minutes. *
The On Time
can only be modified if the ramping function is
disabled
Cycle Time —
The minimum ventilation’s
cycle time can be adjusted from 0 to 99 min-
utes and must be set to a greater value than
the On Time.