background image

 

Mercury Security © 2017 

MS-ICS 

DOC  10107-0053    

REV 1.02 

 Page   1 

 

www.mercury-security.com 

2355 MIRA MAR AVE. LONG BEACH, CA 90815-1755, (562)986-9105 FAX (562) 986-9205 

MS-ICS  
Intelligent Controller 

Installation and Specifications:

 

1.  General 

The MS-ICS is part of Mercury Security's bridging hardware technology for replacing the Software House GCM 
module.  The MS-ICS intelligent controller provides decision making, event reporting, and database storage for 
the Mercury hardware platform.   
The MS-ICS communicates with the host via on-board 10-BaseT/100Base-TX Ethernet port. An alternate host 
10-BaseT/100Base-TX  communication  connection  is  available  by  use  of  the  optional  Lantronix  Micro125 
interface daughter board.   
The MS-ICS connects to the MS-ACS processor via a 34-pin ribbon cable, up to two MS-ACS are supported.  
Standard  Mercury  remote  serial  I/O  panels  may  be  connected  to  the  external  2-wire  RS-485  multi-drop 
communication bus. 
 

 

 
 

MS-ICS 

 

 

J5

1

4

3

2

S1

^|

ON

D7

1 2 3 4 5 6

J8

TR+
TR-

GND

TB2

4

1

BATTERY: BR/CR2330

REPLACE ANNUALLY

GND

TMP

GND

PFL

GND

BAT

TB1

6

1

BT1 3V

CR/BR2330

S2

J4

J2

+12VDC

J1

1

1.75 [44.55]

6.11 [155.19]

8.58 [218.01]

J5: CONNECTION FOR

LANTRONIX MICRO125

ETHERNET MODULE

(PORT 1)

STANDOFF FOR LANTRONIX MICRO125

ETHERNET MODULE: DIAMETER
0.125" X 7/16", 3 REQUIRED
RICHCO, INC. P/N LMSP-7-01

Ø.156
4 PLACES

J2: INPUT

POWER
12VDC

4.91 

[124.71]

5.83 

[148.01]

STATUS

LEDs

DIP

SWITCH

EARTH

GROUND

J1: TO MS-ACS

J4: ETHERNET

JACK

TB2: TO

REMOTE

MODULES

.46 [11.56]

MS-ICS

This device complies with part 15 of the FCC Rules.  Operation 
is subject to the following two conditions: (1) This device may 
not  cause  harmful  interference,  and  (2)  this  device  must 
accept any interference received, including interference that 
may cause undesired operation. 

Summary of Contents for MS-ICS

Page 1: ...n ribbon cable up to two MS ACS are supported Standard Mercury remote serial I O panels may be connected to the external 2 wire RS 485 multi drop communication bus MS ICS J5 1 4 3 2 S1 ON D7 1 2 3 4 5 6 J8 TR TR GND TB2 4 1 BATTERY BR CR2330 REPLACE ANNUALLY GND TMP GND PFL GND BAT TB1 6 1 BT1 3V CR BR2330 S2 J4 J2 12VDC J1 1 1 75 44 55 6 11 155 19 8 58 218 01 J5 CONNECTION FOR LANTRONIX MICRO125 ...

Page 2: ...38 400 baud no encryption no flow control 3 Input Power Wiring The MS ACS requires 12 Vdc for input power and is connected to J2 Pins 1 and 2 are connected to ground and pin 3 is connected to 12 Vdc Observe POLARITY on 12 Vdc input J2 mates with the following housing and uses two crimp contacts Housing Molex 39 01 4030 Crimp contact Molex 39 00 0047 22 28 gauge 39 00 0039 18 24 gauge 4 Cabinet Tam...

Page 3: ...s 1 3 and 5 are turned ON for approximately 1 5 seconds after the hardware initialization has completed then the application code is initialized The amount of time the application takes to initialize depends on the size of the database about 3 seconds without a card database Each 10 000 cards will add about 3 seconds to the application initialization When LED s 1 through 4 flash at the same time d...

Page 4: ... seconds 7 When complete only LEDs 1 4 will flash for 8 seconds 8 The MS ICS board will reboot 8 seconds after LEDs 1 4 stop flashing no LEDs are on during this time 9 IT Security When installing the MS ICS it is important to ensure that it done in a secure manner Upon installation the user accounts to the web configuration page should be created with secure passwords and that all DIP switches are...

Page 5: ...tice Warranty Mercury Security warrants the product is free from defects in material and workmanship under normal use and service with proper maintenance for one year from the date of factory shipment Mercury Security assumes no responsibility for products damaged by improper handling or installation This warranty is limited to the repair or replacement of the defective unit There are no expressed...

Reviews: