Adjusting Static Pressure Set Points
When the high pressure set point is attained, the controller opens the
vent doors according to the timer cycle. When the low pressure set
point is attained, the controller closes the vent doors according to the
timer cycle. The user can define a high and low pressure set point for
the summer and winter seasons.The pressure set points can be adjusted
from 0 to 0.4 inches of water.
Set the function to
VENT DOORS
using the menu select buttons. The
high and low pressure set points
for the winter season are dis-
played.
Press the Edit key. The low pressure set point flashes on the display.
Use the arrow keys to adjust the set point to the desired value.
Press the Edit key once again. The high pressure set point flashes on
the display. Use the arrow keys to adjust the set point to the desired
value.
Press the down-arrow key. The high and low set points for the
summer season are displayed.
Press the Edit key. The low pressure set point flashes on the display.
Use the arrow keys to adjust the set point to the desired value.
Press the Edit key once again. The high pressure set point flashes on
the display. Use the arrow keys to adjust the set point to the desired
value.
3
Adjusting Season Set Points
The season set points are used to determine when the season changes.
When the outside temperature drops below the winter temperature set
point, the controller uses the winter pressure set points defined above.
Setp in winter
Lo .04" Hi .06"