32
Expert-32T rev.03
Expert-32T
MINIMUM VENTILATION CURVE
The user can define a minimum ventilation curve to adjust the minimum
ventilation on time and fan selection automatically over a given time
period. Each curve is defined by ten points. Each point specifies the day
number, on time and fan selection for that day. The herd age value
defines the current day number used by the curve. Once the points are
defined, the minimum ventilation curve must be activated. When the
minimum ventilation curve is activated, the controller adjusts the on time
every hour in a linear fashion between two consecutive points.
1
Specifying Minimum Ventilation Curve
Set the function to
MINIMUM VEN-
TILATION / CURVE
using the menu
select buttons. The current on time
and cycle time are displayed.
Press the down-arrow key in order
to select day 1 menu. The day
number, on time for the first curve
point is displayed.
Press Edit key as required to adjust each parameter in turn. When a
parameter flashes, it can be adjusted using the arrow keys.
Press the down-arrow key to display and adjust the other points of
the curve.
NOTE:
All ten points of the curve must be specified. If you don't need
ten different points, repeat your last minimum cycle for each unneces-
sary point of the curve.
1. day 1
ON 1:00min
ON 1:30min
Cycle 5:00min