61
CTC EcoZenith i555 Pro
rps
-25 -20 -15 -10 -5 0 5 10 15 20 25 30
7.9.3
Settings Heat pump 1-*
Compressor
Blocked (Permitted/Blocked)
The heat pump is supplied with a blocked compressor.
"Permitted" means that the compressor is allowed to
start.
Stop at outdoor temp °C
-22 (-22...10)
This menu relates to settings for the outdoor
temperature at which the compressor is no longer
permitted to operate. The heat pump starts 2°C above
the set value.
Only applies to air/water heat pumps.
Charge pump %
50 (20...100)
The speed of the charge pump is set here.
Refer to the heat pump’s "Installation and Maintenance
Manual" for more information.
Cold temp limit
0 (0...-15)
Temperature limit for "winter power".
When the outdoor temperature is equal or lower (T2),
the compressor speed is adjusted up to speed R2.
Only applies to modulating air/water heat pumps.
Max rps
90* (50...120)
The maximum permissible speed of the compressor at
"winter temperature". Sets the compressor’s maximum
speed (R2) at outdoor temperature T2.
Only applies to modulating air/water heat pumps.
Warm temp limit
20 (0...20)
Temperature limit for "summer power". When the
outdoor temperature is equal or higher (T1), the
compressor speed is adjusted down to speed R1. The
heat pump starts and stops at the actual value and
setpoint value.
Only applies to modulating air/water heat pumps.
Max rps warm temp
50 (50...120)
The maximum permissible speed of the compressor
at "summer temperature". Sets the compressor’s
maximum speed (R1) at outdoor temperature T1.
Only applies to modulating air/water heat pumps.
The diagram shows that the compressor speed is controlled
according to the outside temperature.
When the outside temperature is below T2, the compressor
speed adjusts up to R1.
When the outside temperature exceeds T1, the compressor
speed adjusts down to R1.
These temperature and speed limits are set in the menus on
the left.
*The value may vary depending on the heat pump model.
**CTC EcoZenith i555 can control up to 3 CTC heat pumps and 3 heating circuits simultaneously.
Menu: "Installer/Settings/Heat Pump /Heat Pump 1".
Outdoor °C
Summary of Contents for EcoZenith i555 Pro 1x230V
Page 2: ......
Page 3: ...162 505 72 1 2020 09 22 Installation and Maintenance Manual CTC EcoZenith i555 Pro ...
Page 152: ...152 CTC EcoZenith i555 Pro 18 Wiring diagram relay card 3x400V ...
Page 153: ...153 CTC EcoZenith i555 Pro ...
Page 154: ...154 CTC EcoZenith i555 Pro 19 Wiring diagram relay card 1x230V ...
Page 155: ...155 CTC EcoZenith i555 Pro ...
Page 156: ...156 CTC EcoZenith i555 Pro 20 Wiring diagram relay card 3x230V ...
Page 157: ...157 CTC EcoZenith i555 Pro ...
Page 158: ...158 CTC EcoZenith i555 Pro 21 Wiring diagram for expansion card ...
Page 167: ...167 CTC EcoZenith i555 Pro ...