![CTC Union EcoZenith i555 Pro 1x230V Installation And Maintenance Manual Download Page 26](http://html.mh-extra.com/html/ctc-union/ecozenith-i555-pro-1x230v/ecozenith-i555-pro-1x230v_installation-and-maintenance-manual_2693358026.webp)
26
CTC EcoZenith i555 Pro
Examples of Heating Curves
You can see in the diagram below how the heating
curve changes with different Inclination settings. The
gradient of the curve shows the temperatures that the
radiators require at different outdoor temperatures.
Curve Inclination
The inclination value which is set is the primary flow
temperature when the outside temperature is –15 °C.
Primary Flow Temperature
Primary Flow Temperature
Primary Flow Temperature
Outside Temperature
Outside Temperature
Heating off, out
Outside Temperature
Adjustment
The curve can be parallel displaced (adjusted) by
the desired number of degrees to adapt to different
systems/houses.
An example
Inclination 60 °C
Adjustment 0 °C
In this example, the maximum outgoing primary flow
temperature is set at 55 °C.
The minimum permitted primary flow temperature is
27 °C (e.g. summer-time basement heating or the floor
circuits in a bathroom).
Inclination 50 °C
Adju5 °C
Inclination 50 °C
Adjustment 0 °C
Heating off, out
Summary of Contents for EcoZenith i555 Pro 1x230V
Page 2: ......
Page 3: ...162 505 72 1 2020 09 22 Installation and Maintenance Manual CTC EcoZenith i555 Pro ...
Page 152: ...152 CTC EcoZenith i555 Pro 18 Wiring diagram relay card 3x400V ...
Page 153: ...153 CTC EcoZenith i555 Pro ...
Page 154: ...154 CTC EcoZenith i555 Pro 19 Wiring diagram relay card 1x230V ...
Page 155: ...155 CTC EcoZenith i555 Pro ...
Page 156: ...156 CTC EcoZenith i555 Pro 20 Wiring diagram relay card 3x230V ...
Page 157: ...157 CTC EcoZenith i555 Pro ...
Page 158: ...158 CTC EcoZenith i555 Pro 21 Wiring diagram for expansion card ...
Page 167: ...167 CTC EcoZenith i555 Pro ...