SERENITY – technician Guide
52
Address Description
Default
P147E
Zone is on Soak Test-
If a zone is suspected of being faulty and
is causing false alarms, you can turn it into a Soak Test Zone
and it will still be monitored for alarms (NO beeps or buzzer )
when armed but it won
'
t cause the sirens to sound or report via
any protocol. The Soak Test zone will still be logged in the
event memory however so it is possible to check the activity of
the zone, via the memory. and after a suitable period of no
alarms it can be re-instated as part of the alarm by removing
the Soak Test option
Disable
P148E
Exit Terminator Zone
-
If this option is on, when the zone
unseals during the exit delay (P74) time and then seals again,
the panel will cancel any remaining exit delay time and arm in 3
seconds from the time the zone was sealed.
Disable
7.4: Zones/Zones Response Time
Address Description
Default
P149E
High vibration mode
(50ms)
Disable
P150E
Middle vibration mode
(100ms)
Disable
P151E
Low vibration mode (150ms)
Disable
P152E
Response of 200 ms
Enable
P153E
Response of 250 ms
Disable
P154E
Response of 300 ms
Disable
P155E
Response of 350 ms
Disable
7.5: Zones/Alarms to Output
Address Description
Default
P156E
Zone alarm assigned to output
-
If an Area is Armed and a
zone assigned to that Area activates, the zone can trigger
selected Outputs for local alarm signaling. This location assigns
Zones to Outputs for alarms that occur when in the Full Armed
State
All Zones
Assigned to
outputs 1&2
P157E
Zone stay alarm assigned to output
-
If an Area has Stay
Mode Armed and a zone assigned to that Area activates, the
zone can trigger selected Outputs for local alarm signaling. This
location assigns Zones to Outputs for alarms that occur when
Stay Mode is Armed
All Zones
Assigned to
outputs 1&2
P158E
Zone 24 hour alarm assigned to output
-
If zone is
programmed as one of 24 Hour type zone
[P139]
[P140][P141]
and if it is open then the selected output(s) is activated for
local alarm signalling. In case of standard 24 hour zone [P139]
the output will be active for the full reset time. In case of 24
hour auto-reset zone [P140] the output is deactivated when the
reset time expires or if zone is closed. If zone is a 24 hour fire
zone [P141] then the output will pulse at a rate equals to the
pulse time for that output.
All Zones
Assigned to
outputs 1&2