cGas Detector Analog Transmitter - Operation Manual
NOTE:
If you change the analog output zero and range values, you MUST
recalibrate the analog output. Refer to Section
9.4 Calibrating the Analog Output
.
10 ACCESSORIES
10.1 Splash Guard (Option -S)
The splash guard attaches to the front of the enclosure
to protect the sensor during water spray or washdown
applications. It is factory installed and when attached the
enclosure meets IP54 standards. To calibrate a device
with a splash guard, use the Cal Clip.
NOTE:
The splash guard will slow down the response time of the sensor.
10.2 Calibration Adapter Clip “Cal Clip” (p/n: CET-SGC)
To calibrate a cGas Detector with a factory installed splash guard (Option -S),
attach the Cal Clip around the splash guard to allow the use of both hands
during calibration. The small barb hose fitting accommodates standard or
Teflon tubing of 1/8” (3.175 mm) ID and 3/16” (4.762 mm) ID.
NOTE:
The Cal Clip is designed to prevent entry or exit of air except via the hose
barb fitting, therefore it
must be removed during normal operation
or else the