cGas Detector Analog Transmitter - Operation Manual
Alarms Menu
Press Enter
In the Selected Channel
menu, confirm the correct channel is showing.
Selected Channel
CO2
Press the UP button until you see Selected Alarm
, confirm the correct alarm
level is showing.
Selected Alarm
Low Alarm
If you want to choose a different alarm level (ie. Mid or High), press Enter and
use the UP button to scroll to the next alarm level. Press ENTER and continue.
Selected Alarm
>Mid Alarm
Press the Up button until you see Alarm Setpoint
, confirm the desired number
is showing.
Alarm Setpoint
800 PPM
If you want to enter a different alarm setpoint, press Enter and use the UP and
ENTER buttons to change the number. Press ENTER to confirm and continue.
Alarm Setpoint
>1000 PPM
Confirm?
>1000 PPM
N
>Y
Press the Up button until you see Alarm Direction
, confirm the correct direction -
ascending is used for a CO
2
sensor.
Alarm Direction
ASCENDING
Press the Up button until you see Alarm Hysteresis,
confirm the desired value
is showing.
Alarm Hysteresis
005 PPM CO2
If you want to change the value, press Enter and use the UP and ENTER buttons