cGas Detector Analog Transmitter - Operation Manual
Rev. B | 2020.07
Temperature Adj
>-4.0 degC
Humidity Adj
>+02 %RH
Press ENTER to confirm the value is correct. If you entered the wrong value,
press the UP button to move the cursor to N and press ENTER and reenter the
value.
Confirm?
>-4.0 degC
N
>Y
Confirm?
>+2 %RH
N
>Y
7.10 Set Analog Output Mode
The cGas Detector has one analog output, which is factory configured to output
a signal to a controller or control panel. You can set the analog output to OFF
which will result in a 0 current output and will stop the analog output from
sending a signal to the controller or control panel. This may be useful if you
need to perform maintenance on or replace the transmitter.
NOTE: If the analog output mode is OFF, the gas detector is not in operation.
To set the analog output mode, from the main display, press ENTER.
Enter passcode 3032 using the UP button and ENTER button.
Enter Password
3032
Press ENTER to access the Calibrate Menu.
Calibrate Menu
Press Enter
Selected Channel
CO2
Press the UP button to find Set AO Mode. Press ENTER and change the value
using the UP or DOWN buttons.
•
OFF - the analog output will have 0 current output
•
PEAK - (default) the analog output will transmit a signal according
to the highest gas concentration reading of the cGas Detector
Set AO Mode
OFF
Set AO MOde
>PEAK