30
© 2020 All rights reserved. Data subject to change without notice.
cGas Detector Analog Transmitter - Operation Manual
Rev. B | 2020.07
NOTE:
If a question mark ? is displayed then the system is in a minor fault
and a re-zeroing is recommended. For a list of Fault Codes, refer to Section 12
Troubleshooting.
7.6 Enable / Disable Channels
This setting allows you to enable or disable the gas channel and the temp-
erature and RH readings if configured in the device. Disabling a channel does
not mean information won’t show on the display. If you want the disabled
channel information not to show on the display, you must hide the line. Refer to
Section
7.4.3 Display or Hide Gas Channel, RH and/or Temperature Readings
.
NOTE:
The cGas Detector has one gas channel. Enabling the temperature and
RH only allows the information to be displayed on the display, it will not be sent
to a Controller or BAS/DDC.
A disabled channel will not display gas, temperature or RH readings. A disabled
channel will show on the normal display with four dashes in the middle of the
line:
CO2
---- PPM
CO2
76.4 degF
0 PPM
----%RH
From the main display, press ENTER.
Enter passcode 3022 using the UP button and ENTER button.
Enter Password
3022
Press ENTER to access the Config Menu.
Config Menu
Press Enter
In the Selected Channel menu, confirm the correct channel is showing.
Selected Channel
CH1 CO2