cGas Detector Analog Transmitter - Operation Manual
ELECTRICAL
Power Requirement
16 - 30 VDC, 3 W, Class 2
12 - 27 VAC, 50-60 Hz, 3 VA, Class 2
24V recommended. Refer to Section
6.6 Wiring
Connections
Wiring
24 VDC or 24 VAC (ground referenced) 3-conductor
shielded 18 AWG (or larger) stranded within conduit
Fuses
Automatic resetting thermal
INPUT/OUTPUT
Analog Output
One Linear 4 - 20 mA output, signals gas reading
RH & Temperature
(Option -RHT)
User selectable units, user selectable display or
hide readings on the display, user selectable analog
output (default is the gas reading)
ENVIRONMENTAL
Operating
Temperature
0°C to 40°C / 32°F to 104°F (standard)
Operating Humidity
15 - 90% RH non-condensing
Pollution Degree
Degree 2
Altitude
below 2,000 m