cGas Detector Analog Transmitter - Operation Manual
VDC or 12 VAC.
NOTE: WARRANTY VOID IF SOLID-CORE WIRE IS USED AT THE WIRING
TERMINAL STRIP.
When using solid core wiring for distribution (in the conduit), use stranded wire
pigtails 18 AWG within the enclosure to connect to the circuit board. The rigidity
of solid-core wire can pull a soldered terminal strip completely off a circuit
board and this will not be covered under warranty.
6.6.1 Analog Wire Gauge vs Run Length
The table below shows the maximum cable length between the cGas Detector
and the controller for normal installations (a separate signal line from the
controller for each cGas Detector is required).
SUPPLY
VOLTAGE
MAXIMUM LOAD
(Wire +
Termination
Resistor) (ohms)
WIRE GAUGE
(awg)
MAXIMUM
CABLE LENGTH
(feet)
24 VDC
592
20
4,400
18
7,100
16
10,700
16 VDC
216 (assume a
200 Ω termination
resistor)
20
700
18
1,200
16
1,800
24 VAC
1,060
20
27,000
18
43,200
16
65,500