7.4.2 Display Information - Normal or Minimal
The default display set from the factory is normal mode which displays the gas
type, gas reading and gas units for CH1.
CO2
536 PPM
The information can be reduced to just the gas type by changing the setting to
the minimal mode display.
********-CO2-********
From the main display, press ENTER.
Enter passcode 1014 using the UP button and ENTER button.
Enter Password
1014
Press ENTER to access the Display Menu.
DisplayMenu
Press Enter
Display Type
Normal
Press ENTER. Use the UP button to change the display type and press ENTER
to save and Exit.
Display Type
>Minimal
7.4.3 Display or Hide Gas Channel, RH and/or Temperature Readings
You can choose what reading(s) you want displayed on the screen by hiding or
unhiding lines.
From the main display, press ENTER.
Enter passcode 1014 using the UP button and ENTER button.
Enter Password
1014
Press ENTER to access the Display Menu.
Display Menu
Press Enter